The system shall be electrically supervised for open or (+/-) ground fault conditions in SLC, alarm circuits, and control circuits. Removal of any detection device, alarm appliance, plug-in relay, system module, or standby battery connection shall also result in a trouble signal. Fire alarm signal shall override trouble signals, but any pre-alarm trouble signal shall reappear when the panel is reset.

Detect the activation of any initiating device and the location of the alarm condition. Operate all notification appliances and auxiliary devices as programmed.

Visually and audibly annunciate any trouble, supervisory or alarm condition on operator’s terminals, panel display, and annunciators.

The FACP shall include a full-featured operator interface control and annunciation panel that shall include a backlit, 80 character liquid crystal display, individual, color coded system status LEDs, and an alphanumeric keypad for the field programming and control of the fire alarm system.

The system must comply with UL 9th edition.

The system shall have the following capacities and general operation modes:

  1. Signal Line Circuits (SLCs): Capacity for expansion up to at least 198 total addressable devices per SLC and up to at least 2048 total annunciation points per system. The number of SLCs provided shall be as indicated on the Drawings, with a minimum of (1) one spare for future use.
  2. Digitized Electronic Signals: Shall employ check digits or multiple polling. In general a single ground or open on any system signaling line circuit, initiating device circuit, or notification appliance circuit shall not cause system malfunction, loss of operating power or the ability to report an alarm.
  3. System Response to an Alarm Condition: When a fire alarm condition is detected and reported by one of the system initiating devices or appliances, the following functions shall immediately occur:
    1. The system alarm LED shall flash.
    2. A local piezo-electric signal in the control panel shall sound.
    3. The 80-character LCD display shall indicate all information associated with the fire alarm condition including: the type of alarm point, the initiating device address and the description of its physical location within the protected premises.
    4. History logging of all information associated with the event, including time and date of occurrence.
    5. Activate all system outputs, including program assigned via control-by-event equations, shall be executed by the particular point in alarm. Exact programming shall be provided by the Contractor to meet the Owner’s requirements.
    6. Activate all fire alarm Notification Appliances in the building, sounding and flashing in synchronization continuously until manually silenced, or until the initiating device and control unit has been reset to normal condition.
    7. Activate digital alarm communicator.
    8. Deactivate door hold control relay such that all smoke doors are allowed to close.
    9. Deactivate control relays allowing HVAC units to stop.
    10. Activate elevator recall sequence if smoke is detected in any elevator lobby or in the elevator equipment room.
    11. Release all doors, which may be secured by “fail secure” methods.
    12. Transmission of all data to any remote annunciation panels.
  4. System Response to Trouble Conditions:
    1. The system trouble LED(s) shall flash.
    2. A local piezo-electric signal in the control panel shall sound.
    3. The 80-character LCD display shall indicate all information associated with the trouble condition including: the type of device point, the device address and the description of its physical location within the protected premises.
    4. History logging of all information associated with the event, including time and date of occurrence.
    5. Activate digital alarm communicator.
    6. System AC power trouble signal shall not be sent unless maintained for 8 hours (or more).
    7. Provide adjustable time delay for all trouble signals prior to transmission.
    8. Transmission of all data to any remote annunciation panels.
  5. System Response to Supervisory Conditions (typically associated with sprinkler system monitored type devices only):
    1. The system supervisory LED(s) shall flash.
    2. A local piezo-electric signal in the control panel shall sound.
    3. The 80-character LCD display shall indicate all information associated with the supervisory condition including: the type of device point, the device address and the description of its physical location within the protected premises.
    4. History logging of all information associated with the event, including time and date of occurrence.
    5. Activate digital alarm communicator.
    6. Transmission of all data to any remote annunciation panels.
The FACP shall be capable of providing the following features:

  1. Upload/Download to PC Computer
  2. Charger Rate Control
  3. Drift Compensation
  4. Automatic Day/Night Sensitivity Adjust
  5. Device Blink Control
  6. Pre-alarm Control Panel Indication
  7. NFPA 72 Smoke Detector Sensitivity Test
  8. Walk Test
  9. System and Device Status and History Reports
  10. Periodic Detector Test
  11. Alarm Verification, by device, with tally
  12. Printer and CRT Display Interface
  13. Non-Alarm Module Reporting
  14. Block Acknowledge
  15. Smoke Detector Maintenance Alert – When any smoke detector approaches 80% of its alarm threshold due to gradual contamination.
  16. Control-By-Time and Event
Provide an operator’s terminal, which allows the following minimum functions. In addition, the operator’s terminal shall support any other functions required for system control and/or operation:

  1. Acknowledge (ACK/STEP) Switch
  2. Signal Silence Switch
  3. System Reset Switch
  4. System Test Switch
  5. Lamp Test Switch
On-board communicators shall be acceptable on the condition of total compatibility with the owners receiving station equipment, provides dual line capability one of which is capable of communications via LAN.
The FACP power supply(ies) shall operate on 120 VAC, 60 Hz and shall be adequate to power all equipment and functions in full alarm continuously utilizing only 80% of the rated output. Signal circuits shall each be loaded no more than 80% of their rated capacity. All modules and drivers must be able to withstand prolonged short circuits in the field wiring, either line-to-line or line-to-ground, without damage.
Components include batteries, charger, and automatic transfer circuitry.

  1. Batteries: Shall be completely maintenance free, sealed lead acid type. Battery nominal life expectancy of 3 years, minimum, is required. Battery voltage and capacity shall be determined by the measured load calculations required by the FACP and related connected equipment.
  2. Battery Charger: Solid state, fully automatic, variable-charging-rate type. Provide capacity for 150% of the connected system load while maintaining batteries at full charge. If batteries are fully discharged, the charger charges them completely within four hours. Charger output is supervised as part of system power supply supervision.
  3. Integral Automatic Transfer Switch: Transfers the load to the battery without loss of signals or status indications when normal power fails.
The FACP shall contain a serial interface board to provide an EIA-232 interface between the fire alarm control panel and the UL Listed Electronic Data Processing (EDP) peripherals. The serial interface board shall allow the use of multiple printers, CRT monitors, and other peripherals connected to the EIA-232 ports. In addition, the serial interface board shall  rovide one EIA-485 port for the serial connection to annunciation and control subsystem components; LEDs shall be provided to show operational status. All serial interface input/outputs shall be optically isolated to provide protection from surges and/or earth grounds.
The FACP and any additional specific equipment/hardware, required by the selected manufacture, must guarantee network interface capability with OnyxWorks.
The FACP shall be housed in a UL-listed cabinet suitable for surface or semi-flush mounting. Cabinet and front shall be corrosion protected, given a rust-resistant prime coat, and manufacturer’s standard finish. The door shall provide a key lock and shall include a glass or other transparent opening for viewing of all indicators. For convenience, the door may be hinged on either the right or left side (field-selectable). Where multiple enclosures are required in the same area, the cabinets shall all be the same size and color. Cabinet doors must be electrically bonded to enclosure it serves.
  1. A copy of the final building floor plans with all device locations and assigned system addresses shall be permanently mounted at the location of the main FACP. All AV circuit EOLs, riser cabinets, and Isolation Modules shall also be included on these drawings. A separate sheet shall be provided for each floor. Sheets shall be laminated. Provide legend for symbols.
  2. All external modules required to be mounted at the main FACP location shall be housed in a UL-listed cabinet suitable for surface or semi flush mounting. Cabinet and front shall be corrosion protected, given a rust resistant prime coat, and manufacturer’s standard finish. The door shall provide a key lock. For convenience, the door may be hinged on either the right or left side (field-selectable). Where multiple enclosures are required in the same area, the cabinets shall all be the same size and color. Cabinet doors must be electrically bonded to enclosure it serves.
  3. The system shall be new and furnished with a warranty (parts & labor) of at least one year from the date of final inspection and acceptance by the Owner. Equipment, initiating devices, and alarm appliances shall be arranged as described in the Drawings; annunciator zones shall be configured as described in the Drawings.
  4. All system components shall be attached to walls and ceiling/floor assemblies and shall be held firmly in place (e.g., detectors shall not be supported solely by suspended ceilings). Fasteners and supports shall be adequate to support the required load. Adhesives are not permitted to mount fire alarm system components to building surfaces or structure.
  5. Loops shall be confined to one floor of coverage and shall not include any devices/modules located or serving other floor areas of coverage. Loop 1 shall be assigned to the lowest elevation level of the building. Loop numbers shall increment with elevation levels of the building floors. Device numbering starts the loop with address 001 and increments sequentially accordingly as electrically connected in the circuit to the return of the loop.
    Note: With the written prior approval of UNC Life Safety Systems, multistory buildings with small footprints may be allowed more than one floor per loop.
  6. The FACP must have an Alarm Silence switch, and be equipped with the Subsequent Alarm (alarm resound) feature. Any remote annunciators or graphic displays located away from the alarm area must also include an audible signal with alarm resound feature and must be silenceable from the main panel.
  7. A supervised programmable “Hot Key” for defeating or bypassing all AV circuits, including sounder base units, must be provided in the FACP. The switch must indicate “Normal” or “Off Normal” position.
  8. If the system design includes any type of door control features, a supervised programmable “Hot Key” for defeating or bypassing all door hold open circuits and fire shutter doors or smoke curtains must be provided in the FACP. The switch must indicate “Normal” or “Off Normal” position.
  9. If the system design includes any elevator controlling equipment, a supervised programmable “Hot Key” for defeating or bypassing all elevator capture and shunt trip features must be provided in the FACP. The switch must indicate “Normal” or “Off Normal” position.
  10. If the system design includes AHU shutdown or smoke removal startup, silencing the alarm (without resetting) must not reverse them. A supervised programmable “Hot Key” for all AHU Shutdown Defeat modules must be provided in the FACP. The switch must indicate “Normal” or “Off Normal” position. In addition, provide supervised Hand-Off-Auto switch(es) at the FACP for any building smoke control equipment (pressurization, smoke purge or exhaust fans).
  11. The coverage of each fire alarm loop as described in the Drawings shall be indicated on the FACP and any remote annunciator. This may be accomplished by engraved labels, framed directories, and/or graphic displays. Label tape or handwritten labels are not acceptable.
  12. System shall provide printer data connection.
All fire alarm equipment 120 VAC supply power shall be fed from the facility “Emergency Power” circuit if available. Systems are to be provided with a separate and independent source of emergency power. Switching to emergency power during alarm shall not cause signal drop-out. Batteries must meet the appropriate NFPA capacity requirements, with a 25% safety factor. This requirement is in effect even if generator power is supplied to the Fire Alarm Control Panel.

Provide an engraved label in the FACP identifying its 120 VAC power source. This label shall include panel board location, identification and circuit number.

Provide 120V receptacles for printer use at the main panel. Provide printer data connection at the main panel.

Style 6 Circuits Required: Systems with one or more addressable sub-panels that (1) have an integral addressable loop controller, or (2) monitor multiple conventional initiation zones, shall comply with the NFPA 72 requirements for Style 6 circuits.

All wiring shall be color coded in accordance with the following scheme, which shall be maintained throughout the system, without color change in any wire run:

Addressable Devices Approved Manufacture Data
Signal Line Circuit cable Red jacket with Red(+)/Black(-)
Alarm Indicating Appliance Circuits Blue (+)/Black (-)
Conventional Type Devices or Circuits connected directly to the FACP or to Monitored or
Controlled Addressable Devices
Initiating Circuits, General* Red (+)/White (-)
Initiating Circuits, Smoke Detectors Only* Violet (+)/Gray (-)
AHU Shutdown Circuits Yellow (+)/Brown (-)
Door Control Circuits Orange
Elevator Capture Circuits Brown

All wiring and cable must be in EMT, 3/4″ minimum diameter, unless indicated otherwise on the Drawings or elsewhere in the Specifications. All fire alarm system raceway, couplings, and connectors must meet the performance and installation requirements of Section 16000 “RACEWAYS”. Couplings shall be steel compression type and connectors shall be steel compression type with insulated throats.

All wiring shall be checked for grounds, opens, and shorts, prior to termination at panels and installation of detector heads. The minimum resistance to ground or between any two conductors shall be ten megohms (10 MW), as verified with a megger. Provide advance notice to the A/E of these tests.

Remote Transmissions

Provide a Digital Alarm Communicator Transmitter (DACT) which is fully compatible with the Owner’s Proprietary alarm receiving equipment or the listed central station as indicated on the Drawings. The DACT must be capable of interfacing with the FACP. The following signals, in order of precedence shall be reported as applicable:

  1. Fire
  2. Trouble
  3. Water-flow
  4. Supervisory

The DACT shall be capable of and equipped with:

  1. 4-channel minimum
  2. Backup batteries with an automatic battery charging circuit
  3. Capable of performing a self test every 24 hours and generating a 24 hour test report to the receiving station equipment
  4. Any failure shall initiate a trouble condition. The “Trouble” signal for AC power loss must not be sent unless maintained for 1 hour or more to avoid nuisance transmissions due to
    momentary 120 VAC power outages or alarm verification cycles.
  5. Dual phone line capability
  6. Network connectivity
  7. Any off-normal condition shall be report to the DACT for transmission

*The Bosch 7412G with the D928 dual line phone and DX4020 network interface modules are highly recommended to meet these requirements.

DACTs requiring programming of Electronic memory (i.e, PROM flashing/burning type), are not acceptable.

Auxiliary Power Supply(ies) – General

Typical applications for usage of APS panels include but are not limited to: notification appliance circuits (NAC), door holders, control relays, and sounder base power extenders.

APS – Minimum Requirements

All APS(s) shall operate on 120 VAC, 60 Hz and shall have a continuous rating adequate to power all equipment and functions in full alarm continuously utilizing no more than 80% of the total rated ampere output capacity. All modules and drivers must be able to withstand prolonged short circuits in the field wiring, either line-to-line or line-to-ground, without
damage. All APSs shall be capable of providing the following general requirements, features, and functions when utilized as an integral part of the system:

  1. Each APS utilized in the system shall be supervised individually by the FACP. This may be accomplished by:
    1. On-board means of setting the FACP assigned address.
    2. Utilization of a system addressable monitor type module.
  2. Each APS must capable of supervising all input/output circuitry with on-board LEDs for specific fault indications. On board supervision includes:
    1. AC power failure,
    2. Battery fault,
    3. Ground fault,
    4. Individual output circuit faults,
    5. And any auxiliary power output circuits.
  3. Shall provide multiple regulated and conditioned +24VDC output circuits.
  4. Shall provide at least (1) one +24VDC auxiliary type output.
  5. Shall be capable of being externally triggered or initiated by the FACP, via an addressable control module, for all required output activations.
  6. Shall provide at least (1) Form “C” dry contact or other on board form of dry contact output that will change states during any fault condition detected, for connection to (1) one addressable monitoring device for individual APS, FACP supervision.
  7. Output circuits shall have the capability of being selectively disabled, via on-board switch configurations, during any AC power failures.

Enclosures

The APS shall be housed in a UL-listed cabinet suitable for surface or semi-flush mounting. Cabinet and front shall be corrosion protected, given a rust-resistant prime coat, and manufacturer’s standard finish. The door shall provide a key lock. For convenience, the door may be hinged on either the right or left side (field selectable). Where multiple enclosures are required in the same area, the cabinets shall all be the same size and color. Cabinet doors must be electrically bonded to enclosure it serves.

Both audible and visible alarm signals shall be provided. Visible signals must be the strobe (flash discharge) type, with white or clear lens.

  1. All and each AV circuits shall have a supervised means to individually bypass.
  2. In ADA-designated locations, where placement of additional specialized AV devices are required, those device shall follow the action of the room sounder base.
Shall be located as shown on the Drawings; sounders located outdoors or indoor locations subject to moisture, shall be listed for use in wet locations. Electric sounders shall have the
following specifications:

  1. Voltage: Horns shall operate on 24 VDC nominal.
  2. Programming: Horns shall be field selectable without the use of special tools, to provide slow whoop, continuous, three pulse temporal or interrupted tones. Evacuation signal shall be the ANSI 53.41 three-pulse temporal pattern. Animal quarters and patient areas must be served by chimes. Animal quarters shall have means to bypass chimes with supervised override switch to facilitate testing of system.
  3. Mounting: Ceiling mounted devices are not permitted without specific location approvals by the owner.
Strobes shall be located as shown on the Drawings. Strobes indicated for use exterior to the building or indoor locations subject to moisture, shall be mounted at the indicated elevation and listed for use in wet locations.

  1. Voltage: Strobe lights shall operate on 24 VDC nominal.
  2. Mounting: Ceiling mounted devices are not permitted without specific location approvals by the owner.
Shall be located as shown on the Drawings and shall comply with all applicable requirements for both Audible and Visual.
Where indicated on the Drawings, provide bases with a built-in (local) sounder rated at 85dB minimum. Configure sounder bases such that sounders are activated under conditions as described or otherwise indicated on the Drawings. All areas that require the installation of Sounder Base Units shall be configured to function as follows:

  1. Voltage: The sounder base power shall be supervised by the FACP.
  2. Programming: All areas that require the installation of Sounder Base Unit Devices shall be programmed to perform the following sequence of operation:
    1. The sounder base initiating device shall report the 1st alarm condition to the FACP, which in turn shall sound that individual sounder base and any special ADA AV device additionally required in that area ONLY and be silence-able from the FACP.
    2. The 1st alarm received by the FACP shall initiate the DACT.
    3. All sounder bases shall sound on any general alarm condition initiated by any common area initiating device including: smoke detectors, thermal (heat) detectors, manual stations, water-flow, duct detectors, or by a 2nd or subsequent alarm from any other sounder base initiating device.
    4. Individual sounder bases must and be capable of alarm resound.
    5. The initiating device connected to the sounder base shall be supervised by the FACP.
Shall be 10″ diameter vibrating type located as shown on the Drawings; bells located outdoors shall be listed for use in wet locations. Bells shall have the following specifications:

  1. Voltage: Bells shall operate on 24 VDC nominal.
  2. Mounting: Provide flush mounting devices. Bell mounting elevation shall be as described onthe Drawings.
Remote annunciator indicator lights (RAILs) shall be provided in locations where indicated on the Drawings. In addition, RAILs shall have the following features:

  1. RAILs shall be provided with a key type switch for testing of the annunciated device. Testing device activation shall be accomplished through direct hardwiring to the device NOT through software activation, be program activated, or by any external logic controlling.
  2. Voltage: RAILs shall operate on 24 VDC nominal.
  3. Mounting: Device shall be mounted in/to the wall at the same height requirements per NFPA72 as A/V devices. Do not mount in ceiling tiles. Devices shall be located in the nearest corridor or public area and identified by an engraved affixed label.
Shall be supervised and remotely located as specified on the Drawings.

  1. Unit shall have a back-lit LCD display containing a minimum of (80) eighty characters for alarm annunciation in clear English text.
  2. The LCD annunciator shall display all alarm, trouble, and supervisory conditions in the system and provide duplicate “active” manual switching functions of the FACP, including: Acknowledging, Signal Silencing, System Reset, and Test/Drill.
  3. The annunciator shall be in a lockable cabinet keyed the same as the FACP.
  4. Connections: The annunciator shall connect to a two-wire EIA-485 interface. The two-wire connection shall be capable operation at distances of 6,000 feet. Provide interface to fiber optic cable systems and/or repeater units where such are indicated on the Drawings.
  5. System Capacity: The system shall allow a minimum of four LCD annunciators. In addition to annunciation functions, each LCD annunciator shall be capable of the following software programmed system functions: Acknowledge, Signal Silence and Reset.
Annunciator shall communicate with the fire alarm control panel via an EIA-485 communications loop (four-wire) and shall individually annunciate all zones in the system. System zones shall be as indicated on the Drawings.

  1. Annunciator Indicators: The annunciator shall provide a red Alarm LED per zone, yellow Trouble LED, and Supervisory Trouble LED per zone. The annunciator shall also have an “ONLINE” LED, local piezo sounder, local acknowledge/lamp test switch, and custom zone/function identification labels. Annunciator switches may be used for System control such as, Global Acknowledge, Global Signal Silence, and Global System Reset. All annunciator switches and indicators shall be software programmable.
  2. The annunciator shall be in a key lockable cabinet.

In high rise, complex, or higher square footage facilities, a Graphic Annunciator shall be installed. The University must approve the application and manufacturer of the annunciator.

  1. Annunciator Indicators: The annunciator shall provide a red Alarm LED per zone, yellow Trouble LED, and Supervisory Trouble LED per zone. The annunciator shall also have  an “ONLINE” LED, local piezo sounder, local acknowledge/lamp test switch, and custom zone/function identification labels. Annunciator switches may be used for System control such as, Global Acknowledge, Global Signal Silence, and Global System Reset. All annunciator switches and indicators shall be software programmable.
  2. Framed under glass graphic shall provide a LED lamp zone matrix/grid displaying each type of initiating device (manual stations, smoke detectors, thermal detectors, elevator lobby detectors, water flow, and supervisory) for each floor contained in the facility. The University must approve the specific floor labeling prior to construction. Floor references may vary per facility (i.e. Ground Floor may be referred to as 1st Floor).
  3. The annunciator shall be in a key lockable cabinet.
Where emergency voice communications systems are indicated on the Drawings, provide systems with the following characteristics and features:

  1. One-way voice/alarm systems shall be dual channel, permitting the application of an evacuation signal to one or more zones simultaneously with manual voice paging to the other zones. Communication zones shall be capable of being selected in any combination.
  2. Provide duplicate tone generators, pre-amps, and power amplifiers. Failure of any of these shall automatically result in the defective unit being promptly switched off-line and replaced with the backup so that operation as described elsewhere is uninterrupted.
  3. Normal amplifier power shall be a minimum of 125% RMS of the full speaker load, per channel. For purposes of this calculation, use the amplifier’s continuous two-tone output rating and assume one watt per speaker. A copy of this calculation shall be included with the submittals.
  4. Communications equipment shall be housed in the FACP and/or in adjacent cabinets(s) of matching appearance and size. All connections between the FACP and the voice communications panel shall be made via cables or harness assemblies, which have been prewired and tested by the system manufacturer.
  5. Evacuation signal shall be a “three-pulse” temporal pattern complying with ANSI S3.41-1990.
  6. Existing Wiring: Where existing wiring is reused provide a written guarantee that it is acceptable for use with the equipment provided under this contract. Existing wiring may be used only with the owner’s written permission.
In some cases, the use of non-addressable devices with an addressable monitor type module is acceptable. These areas shall be identified on the Drawing with the acceptable device type for the specific locations. Affected areas may include where:

Temperature Ratings

Non-addressable devices shall be utilized in unconditioned spaces where temperature and/or humidity ranges can exceed the manufactures recommended ratings of the electronic component circuitry for proper operation of addressable type devices. Acceptable substitutions with these non-addressable type devices may include:

  1. Thermal Detection Devices
  2. Manual Stations
  3. Tamper Switches
  4. Duct Smoke Detectors

Harsh Environments

Areas that is environmentally detrimental to addressable type devices. Acceptable substitutions with these conventional type devices may include:

  1. Explosion proof devices
  2. Flame detection devices

Mounting

When using non-addressable type devices monitored with an addressable monitor type modules. Mount addressable monitor type modules in nearest conditioned space and indicate its address on the outside of the enclosure by means of a label.

Unless otherwise indicated on the Drawings all initiating devices shall be individually addressable. Addressable devices shall comply with the following general requirements:

  1. Address Setting: Addressable devices shall provide an address setting means inherent within the device. Devices, which are addressed by the FACP are also acceptable.
  2. Device Identification: Addressable devices shall store an internal specific identifying “type” code that the FACP shall use to identify the type of device.
  3. Temperature Ratings: Addressable devices shall not be utilized in unconditioned spaces where temperature and/or humidity ranges can exceed the manufactures recommended ratings of the electronic component circuitry for proper operation.
  4. Operational Indications: Addressable devices shall provide powered LEDs. LEDs shall flash under normal conditions, indicating that the device is operational and in regular communication with the FACP. LEDs shall be placed into steady illumination by the FACP to indicate that an alarm or off normal condition has been detected. The flashing mode operation of the detector LEDs shall be optional through the system field program. An output connection shall also be provided in the device base to connect an external/remote LED indication of an alarm or off normal condition in specific required locations.
  5. Device Mounting: Unless otherwise specified all devices shall provide the following mounting criteria:
    1. All detectors shall be ceiling-mount.
    2. All other addressable devices, remote LED indicators, remote test switches, and isolation modules shall be wall-mount type.
Unless otherwise indicated on the Drawings all pull stations shall comply with the following additional requirements:

  1. All pull stations shall have a dual-action mechanism requiring two actions to initiate an alarm condition.
  2. All pull stations shall provide a clear visual indication when operated, and shall utilize a key type reset for restoral to normal operation. Pull stations that employ a glass break rod are not acceptable.
  3. An LED shall be provided that shall flash under normal conditions, indicating that the control module is operational and is in regular communication with the control panel.
  4. Construction: Pull stations shall be constructed of Lexan or other material suitable to the installation environment with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in raised letters, 1.75 inches or larger. Stations shall be suitable for surface mounting or semi flush mounting as shown on the plans.
  5. In facilities that are fully sprinklered the University requires additional manual stations located at all exits from the building and at all exits per floor within the building (including rooms that only have outside entrances with no access into the facility such as outside mechanical, electrical, and
    sprinkler riser rooms etc.).
Unless otherwise indicated on the Drawings all smoke detectors shall comply with the following additional requirements:

  1. All smoke detector sensitivity shall be set through the FACP and shall be capable of adjustment in the field through the field programming of the system. Sensitivity shall be capable of being automatically adjusted by the FACP program on a time-of-day basis. Devices shall be capable of reporting obscuration levels and maintenance alerts when any smoke/duct detector approaches 80% of its alarm threshold due to gradual contamination.
  2. In facilities that are fully sprinklered the University requires additional smoke detection in telecommunication closets, electrical closets, and rooms that contain significant electronic equipment such as computer server rooms and audio and/or video projection rooms.
  3. Must be the plug-in type, each having a separate base, to facilitate replacement and maintenance. When installed in a room, detectors shall be oriented so their alarm light is visible from the nearest door to the corridor.
    1. In areas where smoke detector placements are not easily visible a Remote Alarm Indicator Light (RAIL) must be provided, or in areas that will allow, a RED circle shall be painted on the floor directly below the detector with the device system address.
  4. Spot type smoke detectors mounted within 12 feet of a walking surface shall have their built-in locking device activated.
  5. Unless suitably protected against dust, paint, etc., detectors shall not be installed until the final construction clean-up has been completed. Contaminated detectors must be REPLACED by the Contractor at no additional cost to the Owner.
  6. Identification of individual detectors is required. These device numbers, which must also be shown on the shop drawings, shall be permanently affixed to the detector base.  Device labels may not be affixed to the device. Identification labels must be printed labels with black lettering on a clear background. Handwritten labels or labels made from embossed tape are not acceptable.
  7. Smoke detector guards, where indicated on the Drawings shall be Listed for use with the specific model of smoke detector being protected. All smoke detector guards are to have a separate base which must be very securely anchored to wall or ceiling. The cover must be readily removable by the Owner for periodic detector cleaning and servicing but, to prevent unauthorized entry, must be secured to the base by a lock or tamper resistant screws approved by the A/E. Metal guards must be 16 gauge or heavier steel.
  8. Devices used for elevator capture are identified on the Drawings by the designation EL adjacent to the detector. Primary and/or alternate recall points are indicated on the drawings. Elevator capture or control signals must come from the FACP as relayed by control modules. Use of detector auxiliary contacts for elevator capture is not acceptable or permitted.

The fire alarm system shall be equipped with logic method of verifying the presence of smoke.

Alarms from other than spot type smoke detectors must not be delayed by Alarm Verification. Alarm Verification is NOT to be applied to linear beam, duct smoke detectors, elevator lobby and machine room detectors, nor to any software configured “cross zoned” detection devices. When programming the system, activate the automatic drift compensation feature for all spottype smoke detectors. Whether or not to activate the alarm verification feature for such detectors is to be determined by the design engineer/ owner’s representative.

NOTE: Most applications of analog addressable smoke detectors do not require alarm verification to prevent nuisance alarms, unless there are transient ambient conditions, which may create problems. A short operational test period will usually provide information to determine this.

Systems with Alarm Verification must be permanently labeled to indicate that fact.

While a verification cycle is in progress, an alarm, which occurs on another zone, must not cause the verification cycle under way to be restarted or extended. It may have the same effect on the system as a verified alarm.

The equipment must be Listed for Alarm Verification purposes. It must either be installed at the factory, or field programmable and tested by the Manufacturer’s authorized representative.

Unless otherwise indicated on the Drawings all addressable heat detectors shall comply with the design criteria of the conditioned protected space.
Unless otherwise indicated on the Drawings all duct smoke detectors shall be the photoelectric type.

General

The contractor shall mark the direction of airflow on the duct at each duct detector location. Provide duct access doors.

  1. Air duct/plenum detectors must have device remote annunciation. See section “Annunciation Devices”  above for guidelines pertaining to these specific devices.
  2. These detectors shall be installed in a manner that provides suitable access for required periodic cleaning and calibration.

Air Sampling Tubes

The preferred method for providing support is to extend the intake tube through the far side of the duct, seal around the tube where it penetrates the duct wall, and plug the end with a rubber stopper. This facilitates visual inspection, intake tube cleaning, and injection of smoke or equivalent aerosol for testing the detector. Those over 36 inches long must
be provided with center support.

Addressable Monitor Modules shall be provided to connect (1) one non-addressable device or to supervise a non-addressable IDC zone (either Style D or Style B) of conventional type alarm initiating devices (any Normally Open [N.O.] dry contact device) to one of the Fire Alarm Control Panel Signaling Line Circuit Loops. Monitor modules shall be installed as required by the system configuration. All required monitor modules may not be shown on the Drawings.

  1. Indication of Operation: Unless otherwise indicated on the Drawings an LED shall be provided that shall flash under normal conditions, indicating that the Monitor Module is operational and in regular communication with the FACP.
  2. Mounting Requirements: Shall be mounted at the same height requirement as Notification Appliance devices in a clearly visible location.
Addressable Control Modules shall be provided to supervise and control the operation of (1) one conventional Notification Appliance Circuit (NAC) of compatible, 24 VDC powered, polarized Audio/Visual (A/V) Notification Appliances. For fan shutdown and other auxiliary control functions, the control module may be set to operate as a dry contract relay. The control module shall provide address-setting means using decimal switches and shall also store an internal identifying code that the control panel shall use to identify the type of device. An LED shall be provided that shall flash under normal conditions, indicating that the control module is operational and is in regular communication with the control panel. Control modules shall be rated for the load they control. (Inductive Loads require inductive rated modules.)

  1. Mounting Requirements: Shall be mounted at the same height requirement as Notification Appliance devices in a clearly visible location.
  2. Configuration: The control module NAC circuit may be wired for Style Y Class B with up to 1 Amp of inductive A/V signal, or 2 Amps of resistive A/V signal operation, or as a dry contact (Form C) relay. The control module shall be suitable for pilot duty applications and rated for a minimum of 0.6 amps at 30 VDC. The relay coil shall be magnetically latched to reduce wiring connection requirements, and to insure that 100% of all auxiliary relay or NACs may be energized at the same time on the same pair of wires.
  3. Power Source: Audio/visual power shall be provided by a separate supervised power loop from the main fire alarm control panel or from a supervised, UL listed remote power supply. A/V power sources and connections are not shown on the Drawings.
  4. Supervision required: The connection between individual addressable modules and their contact type initiating device(s) must be supervised.
Isolator Modules shall be provided to automatically isolate wire-to-wire short circuits on an SLC loop. The Isolator Module shall limit the number of modules or detectors that may be rendered inoperative by a short circuit fault on the SLC Loop.

Operation

Isolator Modules shall operate such that if a wire-to-wire short occurs, the Isolator Module shall automatically open-circuit (disconnect) the SLC loop. When the short circuit condition is corrected, the Isolator Module shall automatically reconnect the isolated section. The Isolator Module shall not require any address setting, and its operations shall be totally automatic. It shall not be necessary to replace or reset an Isolator Module after its normal operation.

To minimize the impact of a wiring fault on the system, isolation modules must be provided as follows:

  1. After each 25 devices/control points on any addressable circuit.
  2. For each circuit extending outside the building.
  3. In the FACP, at each end of the loop.
  4. On loops containing less than the 25 devices place an isolator at each end of the loop and one in the electrical center of the loop.

Mounting

The Isolator Module shall be wall mounted at the same height as A/V devices in a clearly viewable area in corridors. It shall provide a single LED that shall flash to indicate that the Isolator is operational and shall illuminate steadily to indicate that a short circuit condition has been detected and isolated.

Door hold open magnets shall be furnished with keepers, door chains, and other accessories as required to properly hold open doors as indicated on the Drawings. Holding force of the magnet shall be appropriate for the door to be held open. Door hold open magnets shall operate in a fail-safe manner, i.e., the door shall release in event of a failure of voltage to the device.

Power Supply

Door hold open magnets shall be configured to operate from a nominal 24 VDC system as supplied by the FACP or other power supply listed for the purpose. All hold open magnet supply sources, whether a part of the FACP or whether derived from a separate power supply, shall be supervised. Door hold open magnets which use step-down transformers, 120 VAC, or local relays are not acceptable. Magnets shall release on a power failure.

Device box support

Door hold open magnet device boxes shall be securely attached to the building structure by effective means. Boxes attached directly to only one metal stud or boxes supported by means of expansion type fasteners are not acceptable.

Wall mounted magnetic door holders and separate heavy-duty closers shall be used, instead of combination door control units. The electromagnets shall be controlled by the building’s smoke detection system FACP. Individual smoke detector auxiliary contacts shall not be used to release door holders.

Rolling Fire or Smoke Doors shall be motor operated. No manual reset doors are permitted.

Remote Power Supplies

Where remote power supplies are required, they shall meet the same requirements as those for the main fire alarm control panel, including the requirements for batteries and supervision.

Keys and Locks

All panels, terminal cabinets, and pull stations shall be keyed alike. Coordinate key/lock with the Owner’s requirements.

Automatic door locks controlled by the system must be either fail-safe magnetic locks or failsafe electro-mechanical with reverse bevel dead bolts.

All lock-protected doors must immediately unlock upon fire alarm, loss of AC power, disablement of the fire alarm system (defined as loss of 24 VDC power) or upon manual operation of an unlocked supervised switch at a constantly attended location.

Provide the following spare parts with the system, each individually packaged and labeled. For multi-building projects, calculate separately for each building:

  • Fuses: 2 of each size used in system
  • Isolation Modules: 2% of installed quantity
  • Manual Stations: 2% of installed quantity
  • Indoor Horns/Strobes: 4% of installed quantity
  • Spot Smoke Detectors, Bases: 6% of installed quantity
  • Heat Detectors: 6% of installed quantity
  • Monitor/Relay Modules: 2% of installed quantity

Increase decimal quantities of spare parts to the next higher whole number. For example, if a system has 20 spot-type smoke detectors, provide 2 spare detectors with bases.